ADVR-2300M

Kutai ADVR-2300M Automatic Voltage Regulator (AVR).

Automatic Voltage Regulator (AVR)

Specifications

Sensing InputVoltage 220 to 600 Vac 1 phase or 3 phase DIP switch setting | Frequency 50/60 Hz DIP switch setting
Power InputVoltage 60 to 300 Vac 1 phase 2 wire | Frequency 50 to 500 Hz
Excitation OutputVoltage Continuous 125 Vdc @ power input 220 Vac | Current Continuous 3.5A Intermittent 7A for 10 seconds | Resistance ≧ 18 ohms @ power input 110 Vac / ≧ 36 ohms @ power input 220 Vac
External Voltage AdjustmentMax. +/-5% @ 500 ohms 1 watt potentiometer | Max. +/-10% @ 1K ohms 1 watt potentiometer
Voltage RegulationLess than +/-0.5% (with 4% engine governing)
Build Up Voltage5Vac 25Hz residual volts at power input terminal
Soft Start Ramp Time4 seconds +/-10%
EMI SuppressionInternal electromagnetic interference filtering
Static Power DissipationMax. 6 watts
Burden in Shunt & PMG Wiring550 VA @ power input 110 Vac | 1100 VA @ power input 220 Vac
Quadrature Droop InputCT 1A or 5A greater than 5VA (DIP switch setting) | Sensitivity Max. +/-7% @ P.F +/-0.7
Analogue InputInput resistance greater than 2K ohms | Max. Input +/-5 Vdc or +10 Vdc | Sensitivity 1 Vdc for 2.5% Generator Volts
Under Frequency Protection(Factory Presets)50 Hz system knee point at 45 Hz | 60 Hz system knee point at 55 Hz
Over Excitation ProtectionInverse-time 125 +/-4 Vdc @ power input 220 Vac
Voltage Thermal DriftLess than 3% at -40 to +70 °C

AVR Control Functions

VOLTVoltage adjustment
STABStability adjustment
U/FSetting under frequency protection knee point
DROOPDroop adjustment
TRIMAnalogue input adjustment
DIPVoltage droop ratio setting

Indication LED

O/EOver excitation protection indicator
U/FUnder frequency protection indicator

Environment

Operating Temperature-40 to +60 °C
Storage Temperature-40 to +85 °C
Relative HumidityMax. 95%
Vibration5.5 Gs @ 60 Hz

Physical Specifications

Dimension150.0 (L) x 135.0 (W) x 55.5 (H) mm | 5.91 (L) x 5.31 (W) x 2.19 (H) inch
Weight470 g +/-2% | 1.04 lb +/-2%