ADVR-2300M

3.5Amp Hybrid Analog/Digital AVR for Shunt, PMG/Aux. Winding Genset

ADVR-2300M is a hybrid Analog/Digital AVR which is compatible with Marathon DVR2000 Series. This voltage regulator can be used on single/three phase sensing and Shunt/PMG/Aux.Winding. It has PF (power factor) correction inputs and the facility for droop CT connection.
* It can be used with KUTAI IVT Generator Excitation Booster to increase motor starting capacity.
* If not for use with the IVT Generator Excitation Booster, the ADVR-2100M can be used instead,and purchased at a big discount.
  • Power input single phase 60 to 300 Vac @ 50 to 500 Hz
  • Sensing input 1 or 3 phase 220 to 600 Vac programmable, RMS reading
  • Voltage regulation less than +/-0.5%
  • 50/60 Hz selectable
  • Multiple power input source SHUNT, AUX, HARMONIC, PMG
  • Inverse-time over excitation and under frequency protection
  • Soft start voltage ramping
  • Built-in high capacity protection fuse
  • Panel mounted, internal wiring external adjustment
  • Apply with KUTAI IVT-1260/IVT-2460 to exceeds normal generator motor starting capabilities

Specifications

Sensing Input
  • Voltage 220 to 600 Vac 1 phase or 3 phase DIP switch setting
  • Frequency 50/60 Hz DIP switch setting
Power Input
  • Voltage 60 to 300 Vac 1 phase 2 wire
  • Frequency 50 to 500 Hz
Excitation Output
  • Voltage Continuous 125 Vdc @ power input 220 Vac
  • Current Continuous 3.5A Intermittent 7A for 10 seconds
  • Resistance ≧ 18 ohms @ power input 110 Vac / ≧ 36 ohms @ power input 220 Vac
External Voltage Adjustment
  • Max. +/-5% @ 500 ohms 1 watt potentiometer
  • Max. +/-10% @ 1K ohms 1 watt potentiometer
Voltage Regulation
  • Less than +/-0.5% (with 4% engine governing)
Build Up Voltage
  • 5Vac 25Hz residual volts at power input terminal
Soft Start Ramp Time
  • 4 seconds +/-10%
EMI Suppression
  • Internal electromagnetic interference filtering
Static Power Dissipation
  • Max. 6 watts
Burden in Shunt & PMG Wiring
  • 550 VA @ power input 110 Vac
  • 1100 VA @ power input 220 Vac
Quadrature Droop Input
  • CT 1A or 5A greater than 5VA (DIP switch setting)
  • Sensitivity Max. +/-7% @ P.F +/-0.7
Analogue Input
  • Input resistance greater than 2K ohms
  • Max. Input +/-5 Vdc or +10 Vdc
  • Sensitivity 1 Vdc for 2.5% Generator Volts
Under Frequency Protection(Factory Presets)
  • 50 Hz system knee point at 45 Hz
  • 60 Hz system knee point at 55 Hz
Over Excitation Protection
  • Inverse-time 125 +/-4 Vdc @ power input 220 Vac
Voltage Thermal Drift
  • Less than 3% at -40 to +70 °C

AVR Control Functions

VOLT
  • Voltage adjustment
STAB
  • Stability adjustment
U/F
  • Setting under frequency protection knee point
DROOP
  • Droop adjustment
TRIM
  • Analogue input adjustment
DIP
  • Voltage droop ratio setting

Indication LED

O/E
  • Over excitation protection indicator
U/F
  • Under frequency protection indicator

Environment

Operating Temperature
  • -40 to +60 °C
Storage Temperature
  • -40 to +85 °C
Relative Humidity
  • Max. 95%
Vibration
  • 5.5 Gs @ 60 Hz

Optional Accessories

WR01 AVR wrench

CE Test Standards

EN61204-3:2001
  • CISPR 22 Class B
  • IEC61000-3-2:2005+A1:2800+A2:2009
  • IEC61000-3-3:2008
EN61204-3:2001
  • IEC61000-4-2:2008
  • IEC61000-4-4:2004+A1:2010
  • IEC61000-4-6:2008
  • IEC61000-4-3:2006+A1:2007+A2:2010
  • IEC61000-4-5:2005
  • IEC61000-4-11:2004

Physical Specifications

Dimension
  • 150.0 (L) x 135.0 (W) x 55.5 (H) mm
  • 5.91 (L) x 5.31 (W) x 2.19 (H) inch
Weight
  • 470 g +/-2%
  • 1.04 lb +/-2%
Weight 0.47 kg
Dimensions 15 × 13.5 × 5.55 cm