MX321

Automatic Voltage Regulator

  • MX321 is a three phase sensed Automatic Voltage
    Regulator and forms part of the excitation system for a
    brush-less generator. Excitation power is derived from a
    three-phase permanent magnet generator (PMG), to
    isolate the AVR control circuits from the effects of non-
    linear loads and to reduce radio frequency interference on
    the generator terminals. Sustained generator short circuit
    current is another feature of the PMG system.
  • The AVR senses the voltage in the main generator winding
    and controls the excitation to maintain the generator output
    voltage within the specified limits, compensating for load,
    speed, temperature and power factor of the generator.
    Three phase RMS sensing is employed for superior
    voltage regulation.
  • Adjustable Soft start circuitry is included to provide a
    smooth controlled build up of generator output voltage.
  • A frequency measuring circuit continually monitors the
    shaft speed of the generator and provides under-speed
    protection of the excitation system by reducing the
    generator output voltage proportionally with speed below a
    pre-settable threshold. A further enhancement of this
    feature is an adjustable volts per Hertz slope and voltage
    recovery time, to improve the response of turbo charged
    engines.
  • Current limiting may be included to allow control over the
    amount of sustained short circuit current.
  • Maximum excitation is limited to a safe period by internal
    shutdown of the AVR output device. This condition remains
    latched until the generator has stopped.
  • The AVR includes an over-voltage protection feature with
    internal shutdown of the AVR output device, plus the ability
    to trip an optional excitation circuit breaker if required.
  • Provision is made for the connection of a remote voltage
    trimmer, allowing the user fine control of the generator’s
    output.
  • An analogue input is provided allowing connection to a
    Newage Power Factor controller or other external device
    with compatible output.
  • The AVR has the facility for droop CT connection, to allow
    parallel running with other similarly equipped generators.

 

  • All manufacturer names and numbers are used for reference purpose only and do not imply that any part is the product of these manufacturer.

SENSING INPUT
Voltage 190-264V ac max, 2 or 3 phase
Frequency 50-60 Hz nominal


POWER INPUT (PMG)
Voltage 170-220V ac max, 3 phase, 3 wire
Current 3A/phase
Frequency 100-120 Hz nominal


OUTPUT
Voltage max 120V dc
Current continuous 3.7 A (see note 1)
Intermittent 6A for 10 secs.
Resistance 15 ohms minimum


REGULATION
+/- 0.5% RMS with 4% engine governing (see note 2)


THERMAL DRIFT
0.02% per deg. C change in AVR ambient (note 3)


SOFT START RAMP TIME
0.4 – 4 seconds


TYPICAL SYSTEM RESPONSE
AVR response 10 ms
Filed current to 90% 80 ms
Machine Volts to 97% 300 ms


EXTERNAL VOLTAGE ADJUSTMENT
+/-10% with 5 k ohm 1 watt trimmer (see note 4)


UNDER FREQUENCY PROTECTION
Set point 95% Hz (see note 5)
Slope 100-300% down to 30 Hz
Max. Dwell 20% volts/S recovery


UNIT POWER DISSIPATION
18 watts maximum


ANALOGUE INPUT
Maximum input +/- 5 Vdc (see note 6)
Sensitivity 1v for 5% Generator Volts (adjustable)
Input resistance 1k ohm


QUADRATURE DROOP INPUT
10 ohms burden
Max. sensitivity: 0.22 A for 5% droop 0PF
Max. input: 0.33 A


CURRENT LIMIT INPUT
10 ohms burden
Sensitivity range: 0.5 – 1A


OVER VOLTAGE DETECTOR INPUT
Set point: 300v. Time delay: 1 Sec (fixed)
CB trip coil volts: 10-30 vdc
CB trip coil resistance: 20-60 ohms


OVER EXCITATION PROTECTION
Set point 75 V dc
Time delay 8-15 seconds (fixed)

English Manual Download
Weight 0.25 kg
Dimensions 13.5 × 10 × 4.5 cm