MX341

Automatic Voltage Regulator

  • MX341 is a two phase sensed Automatic Voltage
    Regulator and forms part of the excitation system for a
    brush-less generator. Excitation power is derived from a
    three-phase permanent magnet generator (PMG), to
    isolate the AVR control circuits from the effects of non-
    linear loads and to reduce radio frequency interference on
    the generator terminals. Sustained generator short circuit
    current is another feature of the PMG system.
  • The AVR senses the voltage in the main generator
    winding and controls the power fed to the exciter stator
    and hence the main rotor to maintain the generator output
    voltage within the specified limits, compensating for load,
    speed, temperature and power factor of the generator.
    Soft start circuitry is included to provide a smooth
    controlled build up of generator output voltage.
  • A frequency measuring circuit continually monitors the
    shaft speed of the generator and provides under-speed
    protection of the excitation system by reducing the
    generator output voltage proportionally with speed below
    a pre-settable threshold. A further enhancement of this
    feature is an adjustable volts per Hertz slope to improve
    engine recovery time on turbo charged engines. Soft start
    circuitry is included to provide a smooth controlled build
    up of generator output voltage.
  • Uncontrolled excitation is limited to a safe period by
    internal shutdown of the AVR output device. This
    condition remains latched until the generator has
    stopped.
  • Provision is made for the connection of a remote voltage
    trimmer, allowing the user fine control of the generator’s
    output.
  • An analogue input is provided allowing connection to a
    Newage Power Factor controller or other external devices
    with compatible output.
  • The AVR has the facility for droop CT connection, to allow
    parallel running with other similarly equipped generators.

 

  • All manufacturer names and numbers are used for reference purpose only and do not imply that any part is the product of these manufacturer.

SENSING INPUT
Voltage 190-264V ac max, 1 phase, 2 wire
Frequency 50-60 Hz nominal


POWER INPUT (PMG)
Voltage 140-220V ac max, 3 phase, 3 wire
Current 3A/phase
Frequency 100-120 Hz nominal


OUTPUT
Voltage max 120V dc
Current continuous 2.7 A
Intermittent 6A for 10 secs.
Resistance 15 ohms minimum


REGULATION
+/- 1% (see note 1)


THERMAL DRIFT
0.03% per oC change in AVR ambient (note 2)


SOFT START RAMP TIME
3 seconds


TYPICAL SYSTEM RESPONSE

AVR Response 10 ms
Filed current to 90% 80 ms
Machine Volts to 97% 300 ms


EXTERNAL VOLTAGE ADJUSTMENT
+/-10% with 1 k ohm 1 watt trimmer (see note 3)


UNDER FREQUENCY PROTECTION

Set point 95% Hz (see note 4)
Slope 170% down to 30 Hz


UNIT POWER DISSIPATION
12 watts maximum


ANALOGUE INPUT

Maximum input +/- 5V dc (see note 5)
Sensitivity 1v for 5% Generator Volts (adjustable)
Input resistance 1k ohm


QUADRATURE DROOP INPUT
10 ohms burden
Max. sensitivity: 0.07 A for 5% droop 0PF
Max. input: 0.33 A


OVER EXCITATION PROTECTION
Set point 75 V dc
Time delay 10 seconds (fixed)

English Manual Download
Weight 0.25 kg
Dimensions 13.5 × 10 × 4.5 cm