R438

Automatic Voltage Regulator

  • R438 AVRs
    – Storage : -55°C ; +85°C

    – Operation : -40°C ; +70°C

    – Standard power supply: AREP or PMG.

    – Rated overload current: 8 A – 10 s

    Electronic protection (overload, short-

    circuit on opening of voltage sensing circuit):
    excitation overload current for 10 seconds then return to approximately 1A. The alternator must be stopped (or the power switched off) in order to reset the protection.
    – Fuse : F1 on X1, X2. 8A ; slow – 250V

    – Voltage sensing : 5 VA isolated via trans
    former ;
    • 0-110 V terminals = 95 to 140 V,

    • 0-220 V terminals = 170 to 260 V,

    • 0-380 V terminals = 340 to 520 V.

    – Voltage regulation ±
    0.5%.
    – Normal or rapid response time via
    ST2
    jumper (see below).

    – Voltage adjustment via potentiometer
    P2.
    other voltages via adapter transformer

    – Current sensing (parallel operation): C.T.

    2.5 VA cl1, secondary 1 A (optional).

    Quadrature droop adjustment via

    potentiometer
    P1.

     