EA341

EA341

Kutai EA341 Automatic Voltage Regulator (AVR).

Automatic Voltage Regulator (AVR)

Specifications

Sensing InputVoltage 190 to 264 Vac 1 phase 2 wire | Frequency 50/60 Hz selectable
Power Input (PMG)Voltage 170 to 220 Vac 3 phase 3 wire | Current 3A / phase | Frequency 100 to 120 Hz nominal
Excitation OutputVoltage Max. 120 Vdc @ power input 220 Vac | Current Continuous 2.7A Intermittent 6A for 10 seconds | Resistance Min. 15 ohms
External Voltage AdjustmentMax. +/-10% @ 1K ohm 1 watt potentiometer
Voltage RegulationLess than +/-1% (with 4% engine governing)
Build Up Voltage5Vac residual volts at power input terminal
Soft Start Ramp Time2 seconds +/-10%
Static Power DissipationMax. 12 watts
Analogue Voltage InputInput Resistance 1K ohm | Max. Input +/-5 Vdc | Sensitivity 1V for 5% generator volt
Quadrature Droop InputBurden 10 ohms | Max. Input 0.33A | Max. Sensitivity 0.07A for 5% droop (PF=0)
Over Voltage Detector InputSet Point 300V | Time Delay 1 second (fixed) | CB Trip Coil Volts 10 to 30 Vdc / 0.5 Amp | CB trip coil resistance 20 to 60 ohms
Current Limit InputBurden 10 ohms | Sensitivity Range 0.5 to 1A
Under Frequency Protection (Factory Presets)Set Point 95% Hz | Slope 170% down to 30 Hz
Over Excitation ProtectionSet Point 90 Vdc | Time Delay 10 seconds (fixed)
Voltage Thermal DriftLess than 3% at temperature range -40 to +70 °C

AVR Control Functions

VOLTVoltage adjustment
STABStability adjustment
UFROSetting under frequency protection knee point
DROOPTo set the Droop to 5% at PF=0
TRIMTo optimize analogue input sensitivity
EXC TRIPOver excitation trip level set
DIPHz related voltage DIP set

Environment

Operating Temperature-40 to +70 °C
Storage Temperature-40 to +85 °C
Relative HumidityMax. 95%
Vibration3.3 Gs @ 100 to 2K Hz

Physical Specifications

Dimensions150.0 (L) x 135.0 (W) x 48.0 (H) mm
Weight394 g +/-2%